APPL EYF-400 4-IN MALL COND SEAL
Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EY Series, 4 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple Coated, 9.38 in L x 5.13 in W
Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EY Series, 4 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple Coated, 9.38 in L x 5.13 in W
- For prevent passage of gases, vapors or flames from one portion of conduit system to another
- Appleton® UNILETS® Conduit Sealing Fitting, Dust-Ignitionproof Explosionproof Raintight, Series: EY Series, 4 in, For Use With: IMC/Threaded Rigid Metallic Conduit, Malleable Iron, Triple Coated, 9.38 in L x 5.13 in W
- Accurately tapped, tapered NPT threads for tight, rigid joints and ground continuity
Removable nipple in male sealing fitting may be used interchangeably in top or bottom hub
Restrict any explosion to the sealed off enclosure
Required in Class I, Division 1 and 2 locations within 18 in of enclosures containing apparatus that may cause arcs, sparks or high temperatures
Required in Class I, Division 1 and 2 locations where 2 in or larger conduit enters enclosure, fitting housing terminals, splices or taps
Required in Class I, Division 1 and 2 locations at the boundary where conduit leaves classified location
Required in Class I, Division 1 and 2 locations where two or more enclosures are connected by 36 in or less conduit, seal must be located within 18 in of either enclosure
Required where cables which exceed rate of gas or vapor transmission permitted for seals are used in Class I, Division 2 locations
25% fill vertical and horizontal conduit sealing fittings for close turning radius
Chromate/epoxy powder coated/zinc electroplated finish
- FITTING SEG CONDUIT 4IN MI
- Product Catalog Page(s)
Specification Sheet
- UL 886|UL 1203 File No. E10444|CSA C22.2 No. 30|CSA 065181|Class I, Groups B, C, D|Class II, Groups E, F, G|Class III
- Brand:Â AppletonApplication:Â For Use With Threaded Rigid Metal Conduit And IMCConnection:Â Female ThreadedCountry of Origin:Â MXFinish:Â Triple-Coat (Zinc Electroplate, Chromate And Epoxy Powder Coat)Material:Â Malleable IronSize:Â 4 inStandard:Â UL 886 (1203), UL File Number E10444, CSA C22.2 No. 30, CSA 065181, UL Listed For Class I, Groups B, C, D; Class II, Groups E, F, G; And Class IIISub Brand:Â UniletsType:Â EY Series 25 PCT Fill Vertical And Horizontal Conduit Sealing Fitting